Drawings and application state 400 amp transfer switch. Highlighted spec sheet shows 200 amps.
Still pending mdl 6/21/23
Still pending mdl 8/14/23
Miscellaneous/Other
Resolved
09/14/2023
Is the existing service a meter can only, or is it a meter main combo? If meter main, indicate the size of the main(s). The ATS selected (RXSC200A3) is a non-service rated switch. Depending on the information provided the ATS may have to be service rated (RXSW200A3).
Still pending mdl 6/21/23
Per the drawing submitted, the ATS should be a service rated transfer switch. A non-service rated switch was submitted mdl 8/14/23.
Drawings and application state 400 amp transfer switch. Highlighted spec sheet shows 200 amps.
Still pending mdl 6/21/23
Still pending mdl 8/14/23
Miscellaneous/Other
Resolved
08/14/2023
Maximum breaker size for 48 kw generator is 200 amps.
application states 400 amp transfer switch, load shedding is required mdl 6/21/23
Miscellaneous/Other
Resolved
08/14/2023
Provide load calculations and load shedding as necessary to comply with NEC 702.4(B)(2).
Still pending mdl 6/21/23
Miscellaneous/Other
Carried Forward
08/15/2023
Is the existing service a meter can only, or is it a meter main combo? If meter main, indicate the size of the main(s). The ATS selected (RXSC200A3) is a non-service rated switch. Depending on the information provided the ATS may have to be service rated (RXSW200A3).
Still pending mdl 6/21/23
Per the drawing submitted, the ATS should be a service rated transfer switch. A non-service rated switch was submitted mdl 8/14/23.
Application says "TO BE LOCATED ON ALUMINUM STAND ABOVE FLOOD". Site plan has the stand at 3' tall. Topographic data has grade at 3.5' NGVD in an AE8. Correct the submittal so the stand is elevated a minimum of 5.5' from grade or provide data from a certified surveyor showing alternate grade elevation data. Stand must meet DFE (9' NGVD).
6/13/2023
Not resolved
Drawings and application state 400 amp transfer switch. Highlighted spec sheet shows 200 amps.
Still pending mdl 6/21/23
Miscellaneous/Other
Carried Forward
07/11/2023
Maximum breaker size for 48 kw generator is 200 amps.
application states 400 amp transfer switch, load shedding is required mdl 6/21/23
Miscellaneous/Other
Carried Forward
07/11/2023
Provide load calculations and load shedding as necessary to comply with NEC 702.4(B)(2).
Still pending mdl 6/21/23
Miscellaneous/Other
Carried Forward
07/11/2023
Is the existing service a meter can only, or is it a meter main combo? If meter main, indicate the size of the main(s). The ATS selected (RXSC200A3) is a non-service rated switch. Depending on the information provided the ATS may have to be service rated (RXSW200A3).
Still pending mdl 6/21/23
Application says "TO BE LOCATED ON ALUMINUM STAND ABOVE FLOOD". Site plan has the stand at 3' tall. Topographic data has grade at 3.5' NGVD in an AE8. Correct the submittal so the stand is elevated a minimum of 5.5' from grade or provide data from a certified surveyor showing alternate grade elevation data. Stand must meet DFE (9' NGVD).
6/13/2023
Not resolved
Drawings and application state 400 amp transfer switch. Highlighted spec sheet shows 200 amps.
Miscellaneous/Other
Carried Forward
06/06/2023
Maximum breaker size for 48 kw generator is 200 amps.
Miscellaneous/Other
Carried Forward
06/06/2023
Provide load calculations and load shedding as necessary to comply with NEC 702.4(B)(2).
Miscellaneous/Other
Carried Forward
06/06/2023
Is the existing service a meter can only, or is it a meter main combo? If meter main, indicate the size of the main(s). The ATS selected (RXSC200A3) is a non-service rated switch. Depending on the information provided the ATS may have to be service rated (RXSW200A3).
Application says "TO BE LOCATED ON ALUMINUM STAND ABOVE FLOOD". Site plan has the stand at 3' tall. Topographic data has grade at 3.5' NGVD in an AE8. Correct the submittal so the stand is elevated a minimum of 5.5' from grade or provide data from a certified surveyor showing alternate grade elevation data. Stand must meet DFE (9' NGVD).